The great copper windings versus aluminum windings debate goes on. It’s
a topic that I first wrote about in 1988. It remains a topic of discussion
today as engineers in a variety of industries question whether the quality
and performance of aluminum windings can possibly compare with copper.
What’s interesting to me is one source of the debate. Some of us
remember the 1960s, when aluminum house wiring was the subject of much
attention because of the apparent fire hazards it created. It turned out
that the cause of the house fires was not the wire itself, but rather
connection problems. The junctions would become so hot that the heat would
transfer to the wire itself, eventually deteriorating the wire insulation.
Consequently, all forms of aluminum wire received a bad rap. This is unjustified:
aluminum can be a perfectly good material for motor windings in many applications.
Aluminum is a good conductor and, when applied properly, performs quite
well. There are, however, two factors to keep in mind.
First, aluminum’s conductivity is lower than copper. To compensate,
aluminum magnet wire must have larger cross-sections than the equivalent
copper wire to offer the same conductance. This means windings wound with
aluminum wire will likely have greater volume compared with an equivalent
copper wire motor.
The second consideration is properly connecting the ends of the aluminum
magnet wire. The reason for this goes back to your high school chemistry
course. You may remember that aluminum oxidizes much faster than other
metals—in fact, if exposed to air, powdered aluminum will completely
oxidize in a few days, forming a fine white powder. But, when exposed
to air, fabricated aluminum (sheets, wire, etc.) tends to form a hard
insulating oxide layer that stops the oxidizing process.
To make a proper connection that ensures conductivity, the oxide layer
of the aluminum magnet wire must be completely pierced and yet pierced
in such a way to prevent air from coming in any further contact with the
aluminum. Motor manufacturers have developed high-pressure, piercing crimp
connectors to do the job. These improved connection methods have helped
make motors with aluminum windings every bit as reliable as motors with
copper windings.
It must be pointed out that motor efficiency is a much trickier issue
in the great copper versus aluminum debate. It is possible to match the
power performance of a motor wound with aluminum to a motor wound with
copper wire. But since aluminum requires more turns and/or a larger diameter
wire, this may not always be economically feasible in some applications.
In situations where efficiency and volume are not issues (such as where
the motor only has to work occasionally or for very short periods of time),
aluminum magnet wires make an acceptable motor.
The bottom line is that, in terms of motor quality, reliability, and life
span, aluminum windings can be every bit as good as copper-wound motors.
Comparisons are fair as long as you keep efficiency issues apart when
looking at copper versus aluminum.
by Neil Simon, aka the Motor Doctor - regional sales
manager for A. O. Smith Electrical Products Company.
|